DF1
to DH+ Passthru using WinLinx or RSLinx
SLC 5/04 processors
(OS401 and greater) support DF1 to DH+ Passthru. With this feature, you
can connect to a 5/04 processor through Channel 0 using the DF1 protocol
and access any node on the DH+ network, regardless of the baud rate of the
DH+ network. It is also possible to connect a modem to Channel 0 and
connect to any node on the DH+ network via modems.
At this time only PanelView devices at FRN 3.3 or higher can be
accessed using the SLC 5/04 passthru. Pre FRN 3.3 PanelViews do not
recognize PCCC messaging which is the protocol used on the DH+ side of the
SLC. An alternate bridge solution would be a 1770-KF2. The customer should
consult their local distributor for other hardware, serial to DH+ bridge,
solutions or firmware upgrades.
To use this functionality with the RSLogix 500 software, you need to use
the following procedure:
PROCESSOR SETTINGS:
RSLogix500
1) Configure Channel 0 of the 5/04 processor for System Mode using
Full-Duplex. This can be done by accessing the Channel Configuration
Window and choosing the appropriate settings.
**Note the Passthru Link ID setting for Channel 1 (which is 2) and Channel
0 (which is 1). If channel's 1 and 0 have the same link ID's then RSLinx/RSWho
will not see through to the DH+ network.

2) You must then access the Chan 0 Tab on the Processor Status File and disable
the DH485 to DH+ Passthru and enable DF1 to DH+ Passthru by setting
both S:34/0 AND S:34/5 high. Note: If you want to view active DH+ nodes in
the 5/04 status table, S:34/1 must also be set.

The above settings must then be downloaded to the processor using either
Winlinx or RSLinx. Once the program has been downloaded, comms drivers
must be altered as detailed below to see the entire DH+ network. Also note
that the driver verification in Winlinx and Auto-Configure in RSLinx will
no longer function correctly since DF1 packets are being passed through
Chan 1. Both functions will still determine the baud rate, but
acknowledgements will no longer be received causing the error checking to
fail.
COMMUNICATION
SETTINGS:
WinLinx
The uLogic/KF3/CH0 driver was initially used to download the project to
the 5/04. This driver must be deleted from Winlinx and the KF2/KE driver
must be used instead. Be sure to set the correct baud rate and turn on the
Don't Verify Settings radio button. Click OK to accept the driver changes.
The SuperWho screen will poll address 1-77 and display any active DH+
nodes.

RSLinx v1.7
To download the program, recall that the Device Type option was initially
set to SLC-CH0. Change this to KF2/KE and click on OK.

Select Communications > SuperWho and 'right-click' anywhere inside the
Who screen and choose Configure SuperWho. In the dialog box, change the
Station Update Mode from Graphical (default) to Normal and click OK. The
resulting Who screen will begin polling from node 1 thru 77 octal and
display all devices connected to the DH+ network.

Remember, the RSLogix500 Who configuration is separate from the RSLinx Who
configuration. Be sure that the Normal mode is chosen in both
configurations.
Note: RSLinx 1.7 requires that one of the nodes on the DH+ network be
set to station 1. If none of the nodes are set to 1 nothing will appear in
the SuperWho. This is not a requirement for RSLinx revision 2.1.
RSLinx v2.0
Once the program has been downloaded, in the driver configuration dialog,
change the Device Type to 1770-KF2/1785-KE and click OK. Click Close to
save the change. If Autobrowsing is enabled, the RSWho will automatically
poll the DH+ network using your AB_DF1 driver.

Note: RSLinx 2.0 requires that one of the nodes on the DH+ network be set
to station 1. If none of the nodes are set to 1 nothing will appear in the
RSWho. This is not a requirement for RSLinx revision 2.1 (or higher).
Posted 23 July 2001
|